Product description
-
The product equipped the HV load switch and HV fuse in transformer oil .It has common box or separate box with transformer body. Oil tank is enclosed sealed with oil temperature gauge, oil level indicator, pressure gauge , pressure relief valve ,drain oil valve etc to monitor the transformer working conditions.The product has loop feed ,radial feed & power supply type.In order to make this product more suitable for the actual requirements of power grid , we have also introduced plug-in type dry type fuse which fusing do not affect the transformer oil. According to the complexity of low voltage outgoing requirements,YB27 enclosure has standard type, intensive and comprehensive type to make user choice more economic & flexible.
Model
Service conditions
-
1.Ambient air temperature: -30℃~+50℃
2.Altitude : Maximum installation altitude: 2500m
3.Outdoor wind speed is not more than 34m/s;
4.Relative humidity: daily average value ≤95%, the monthly average value ≤ 90%;
5.Inclination of installation site : not more than 3 °;
6.Installation site: no explosion danger, serious pollution, chemical corrosion , severe vibration
Products advantage:
-
1.Compact structure, small volume, is only about the 1/3 – 1/5 of the same capacity european type substation, which greatly reduce the occupation area
2.Fully sealed and fully insulated structure, no need insulation distance .
3.The wiring connection of high voltage can be used in loop feed and radial feed. Power supply method is flexible and reliable.
4.Excellent performance; low consumption, low noise, low temperature –rising, high overload, anti short-circuit, high impact resistance, reliable protection of personal safety
5.Meet all kinds of low voltage outgoing requirements .
6.Cable head has 200A elbow plug & 630A “T” shape fixed type. All insulated Zinc Oxide lightning arrester can be configured. 200A cable head can be plugged in with load, also can be acted as isolation switch.
Products structure:
2. Pressure gauge
3. Pressure relief valve
4. Oil level indicator
5. Oil temperature gauge
6. Load break switch
7. High voltage cable connector
8. Off load tap changer
9. Grounding points
10. Drain valve
11. Low voltage switchgear
Technical parameter
|
Item |
Unit |
Parameter |
|||
High Voltage Unit |
Rated frequency |
Hz |
50/60 |
|||
Rated Voltage |
kV |
11 |
13.8、15 |
20、22 |
30,33,36 |
|
Max service voltage |
kV |
12 |
17.5 |
24 |
40.5 |
|
Rated current |
A |
400、630、1250、1600、2000、 |
||||
transformer current |
A |
400~2500 |
|
1min power frequency withstand voltage to earth and phase |
kV |
42/48 |
48/55 |
55/65 |
85/95 |
BIL: to earth and phase to phase |
kV |
75/85 |
90/105 |
125/150 |
170/185 |
|
Rated short circuit breaking current |
kA |
25、31.5、40 |
||||
Transformer Unit |
Rated Voltage |
kV |
11、13.8、15、20、22、30、33、36 |
|||
Rated Capacity |
kVA |
160~1250 |
||||
Tap ranging |
% |
+/-2x2.5%、+/-5% |
||||
Vector Group |
|
Yyn0、Dyn11 |
||||
Impedance |
% |
4、4.5、6、8 |
||||
Low Voltage Unit |
Rated Voltage |
V |
220、400、690、800 |
|||
Main circuit rated current |
A |
400~2500 |
||||
Branch current |
A |
63~1250 |
||||
Enclosure |
Protection Level |
|
HV Room:IP44 |
|||
Noise level |
dB |
≤50 |
Structure characteristics
-
The enclosure structure is made of channel steel and angle steel which has higher mechanical strength. The enclosure is made of aluminum alloy plate ,its face is even and smooth . The product is elegant appearance with better anti-erosion. The foundation of substation is higher 300- 600 mm than ground. All the doors are opened outward with angle more than 90°. The substation has handle, dark latch and dormant lock with waterproof anti-blocking and anti rust.
-
The body is whole enclosed against theft to ensure the working under a common air temperature, the temperature of all electrical devices do not be more than the max. allowed temperature of itself. It is equipped with enough natural vents and insulation measures.The prefabricated transformer substation is equipped with special grounding conductor .On the grounding conductor ,there has terminals to connect with ground net .Its number is more than two pieces and has obvious grounding mark. The ground terminal is copper bolt with diameter more than 12mm. The grounding conductor adopts copper strip which current density can not be more than 200A/mm, the cross section is more than 30mm , to ensure that the flow through the maximum short-circuit current does not overheat or affect the safety of the surrounding objects. Dynamic and thermal steady current of the special grounding conductor should be equipped with grounding methods of H.V. power distribution devices.
Transformer performance parameter
No |
Capacity |
Rated voltage |
Tap |
No load current (%) |
Losses(W) |
Impedance |
|||||
kVA |
HV |
LV |
S9 |
S11 |
No load |
Load |
|||||
S9 |
S11 |
S9 |
S11 |
||||||||
1 |
30 |
6.6 |
0.4 |
+/-5 |
2.2 |
2.0 |
130 |
600 |
4 |
||
2 |
50 |
2.0 |
1.8 |
170 |
870 |
||||||
3 |
63 |
1.9 |
1.5 |
200 |
1040 |
||||||
4 |
80 |
1.7 |
1.2 |
250 |
1250 |
||||||
5 |
100 |
1.6 |
1.1 |
290 |
1500 |
||||||
6 |
125 |
1.5 |
1.0 |
340 |
270 |
1800 |
|||||
7 |
160 |
1.4 |
1.0 |
400 |
310 |
2200 |
|
||||
8 |
200 |
1.4 |
0.8 |
480 |
375 |
2600 |
|||||
9 |
250 |
1.2 |
0.8 |
560 |
400 |
3050 |
3000 |
||||
10 |
315 |
1.1 |
0.7 |
670 |
475 |
3650 |
3600 |
||||
11 |
400 |
1.0 |
0.7 |
800 |
570 |
4300 |
4200 |
||||
12 |
500 |
1.0 |
0.6 |
960 |
680 |
5100 |
5000 |
||||
13 |
630 |
0.9 |
0.6 |
1200 |
800 |
6200 |
6000 |
4.5% |
|||
14 |
800 |
0.8 |
0.6 |
1400 |
1120 |
7500 |
7400 |
||||
15 |
1000 |
0.7 |
0.5 |
1700 |
1320 |
10300 |
9860 |
||||
16 |
1250 |
0.6 |
0.5 |
1950 |
1360 |
12800 |
12000 |
||||
17 |
1600 |
0.6 |
0.5 |
2400 |
1840 |
14500 |
14000 |
a. According to customer requirements, the high voltage tap range of transformer can be designed to be + 2 * 2.5%.
b. According to customer requirements, the transformer low voltage can be designed as 0.69kV
Load break switch parameter
Rated Current (A) |
Rated Voltage (kV) |
BIL |
Power frequecny |
Rated short - time withstand current |
Short circuit making current |
Rated withstand current (peak) |
Load |
Mechanical |
315 |
11 |
75 |
42 |
12.5/2 |
31.5 |
31.5 |
100 |
2000 |
630 |
11 |
75 |
42 |
16/4 |
40 |
40 |
100 |
3000 |