12KV/24KV Indoor High Voltage SF6 Gas Load Break Switch (LBS)
BRFLN36 series indoor high-voltage SF6 load break switch, It is widely used in 11~24kV electric power distribution system , adopted with SF6 gas as an arc-extinguishing and insulation medium
Share This Product:
  • PRODUCT DETAILS
  • Installation&Maintenance

Product description

  • BRFLN36 series indoor high-voltage SF6 load break switch, It is widely used in 11~24kV electric power distribution system , adopted with SF6 gas as an arc-extinguishing and insulation medium, including the three contactors for switching-on and switching-off and to-ground, and is characteristic in its small volume, its convenient installation and operation and its the great adaptability with surroundings.

  • Indoor high-voltage SF6 load break switch and SF6 load break switch plus fuse combination can function to protect and control the electric equipments for power supply and transformer substations especially being suitable for ring net cabinet, cable branch cabinet and distribution switching substation. indoor high-voltage SF6 load switch and SF6 load break switch plus fuse combination are complied with the standards of IEC60265-1-1998, IEC60420 etc.

Service environment

  • a)Air temperature
    Maximum temperature: +40℃; Minimum temperature:-35℃
    b)Humidity
    Monthly average humidity 95%; Daily average humidity 90% .
    c)Altitude above sea level
    Maximum installation altitude: 2500m
    d)Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
    e)No frequent violent shake

Main Specification & Technical Data

No.

Technical Name

Unit

Model

BRFLN36-12/630

BRFLN36-12D/125-31.5 switch-fuse combinations

BRFLN36-24/630

BRFLN36-12D/125-31.5 switch-fuse combinations

1

Rated voltage

KV

12

24

2

Rated Frequency

Hz

50/60

50/60

3

Rated current

Amp

630

125

630

125

4

Rated Insulation Level

1 min power-frequency withstand voltage (KV)

42

55

(Peak) KV

75/85

125/150

5

Rated thermal current (2S)

KA

20

20

6

Rated dynamic current

KA

50

63

7

Rated short-circuit on-off current

KA

25

25

8

Rated closed loop breaking current

A

630

630

9

Rated active on-load breaking current

A

630

630

10

Rated cable charger breaking current

A

10

10

11

Rated short-circuit breaking current(peak)

KA

50

63

12

Rated transfer current

A

1700

1000

13

Fuse type



Sfldj-12


Sfldj-12

14

Impact output energy

J

1+0.5

1+0.5

15

Rated thermal current(2S)for grounding switch

KA

20

2

20

2

16

Rated dynamic current (peak)for grounding switch

KA

50

Maximum torque operated manually

50

Maximum torque operated manually

17

Rated short-circuit on-off current for grounding switch

KA

50

50

18

Mechanical life

Load switch

times

5000

5000

Grounding switch

times

2000

2000

19

(Zero gauge pressure)on-off rated current times

times

10

10

10

10

20

The air distance to the earth and distance between electrified body

mm

More than 125 mm

More than 275 mm

21

SF6 Air Pressure (20 relative pressure)

Bars

0.45

0.45

0.45

0.45

22

Synchronism of switching on and off

ms

2

2

2

2

23

Loop resistance

U

100

100

100

100

24

Max. torque operated manually

NM

Less than 75

Less than 75

25

Operated motor rated voltage

V

AC / DC 110V 220V

AC / DC 110V 220V

26

On-off electric –magnetic steel operation voltage

V

AC / DC 110V 220V

AC / DC 110V 220V

Outline Dimension

  • Side View BRFLN36-12kV Type SF6 Load Break Switch (LBS)
  • Side View BRFLN36-24kV Type SF6 Load Break Switch (LBS)
  • Front View Load Break Switch
  • Block Diagram for BRFLN36 type SF6 Load Break Switch

Structure & Principle

The main loop structure for load break switch
BRFLN36 type indoor SF6 load break switch & its composite apparatus, its main loop partially is sealed in an insulating shell made of epoxy resin. This insulation shell adopts APG process injection, which has advantages of high insulation and antipollution environment etc. The insulation shell is its upper & lower 2 insulation cover pieced together. Inside there has relative pressure 0.45bars SF6 gas. Its lower insulation cover takes some anti-explosion thicker film measures to avoid the high pressure gas release explosion in case of failure to prevent the operator and other parts.
BRFLN36 type indoor high voltage SF6 load break switch and its combination electrical has on, off and grounding 3 positions.

Arc extinguishing principle
BRFLN36 type load break switch take its inside SF6 gas as insulation & arc extinguishing medium. When it switches off, the arc goes to rotate under the magnetic field produced by permanent magnet, then cools under the SF6 gas till it is extinguished.

Operating Structure & inter-lock

  • For BRFLN36 type indoor high voltage SF6 load break switch & its composite apparatus, its operating structure is with K type & A type spring institutions. If equipped with K type spring institution, it is mainly used for incoming unit. If equipped with A spring institution, it is mainly used for outgoing unit and transformer protection.

  • Attention: Only when this SF6 LBS in off position, its switch-on or grounding work can be operated !

Grounding switch operation
  • Operate the grounding switch when switch off
  • Switch when switch onOperate the grounding
Main switch operation
  • operate main switch when switch on
  • Operate the main switch when switch off
Inter-lock
  • When load break switch in switching on, can not switch on the grounding switch, and the lower door can not be opened
  • When grounding switch is switched on, the load break switch can not be switched on
  • When grounding switch is switched on, the load switch can not be operated switching on
  • When grounding switch is off and door closed, the load switch can be switched on
  • For composite electrical switchgear cabinet, if any phase fuse blow, its impactor can let the load switch in reliable switching off. In this time ,can not switch on the load switch, can not keep it in on position too.

a)Installation & testing

  • All BRFLN36 type LBS are strictly inspected before off the Boerstn factory, which comply with the standard and technical requirements. Before the installation & testing, must carefully read the installation & usage instructions, and work as following:

  • 1.Check if the appearance is damaged. If so ,should stop the usage
    2.Clear and get rid of the dirt on its face because of transport of other reasons
    3.After installation well ,must be sure that the load switch in off position. If so, insert the operation handle into the grounding holes on its upper board ,then rotate clockwise 180 to switch on the grounding. Anti-clockwise 180 to off the grounding.
    4.When go to do the work of switching –on, firstly let the load switch be off position, then insert the operation handle into the operating hole of the load switch in lower board
    5.Operating From switch-on to switch off, For K type spring institution: insert the operation handle into the hole of load switch, anti-clockwise rotate 180 to do the off-switch.
    For A type spring institution, push the switch-off button to off the switch. Inspect the switch position through its viewing window, and watch its indication comply with the requirements or not.

  • Attention: Only when the switch in off position, can go to switch on the grounding or load.

Maintenance

  • If the product is in accordance with the requirements of the installation instructions & environment ,it can be in 10 years free maintenance and can reliable work for 25 years. But per each year ,must do the necessary inspection and maintenance.

  • 1.Inspect the appearance of its insulation cover, get rid of its dirt on face.
    2.Conduct 3-5 lubrication and operation checks on the operating mechanism
    3.Check the readings of the pressure gauge on load switch. When readings is lower than 0.01Mpa, it should be filled gas in time. The work of filling gas should be done by professional work or from the factory.
    4.When load break switch + fuse composite apparatus is damaged ,one phase fuse blow, then must replace all 3 phase fuses. Before replacement, must switch on the grounding switch

  • Attention:
    Unless the Boerstn's representative is present, otherwise It is strictly forbidden to remove the self-sealing valve (pressure connector)of the switch body
    In any time it is forbidden to self-remove the sealing screws of the upper or lower unit of the switch cover.

Feedback form contact with us
Related Product
ZN63A(VS1)-12~24KV  Indoor Vacuum Circuit Breaker (VCB)
ZN63A(VS1)-12~24KV Indoor Vacuum Circuit Breaker (VCB)
Product description This technical condition specifies the ZN63A(VS1) indoor AC medium-voltage vacuum circuit breaker in terms of ...
ZN85-40.5KV Indoor Vacuum Circuit Breaker (VCB)
ZN85-40.5KV Indoor Vacuum Circuit Breaker (VCB)
The use of environmental conditions Altitude: ≤2000m; Air temperature: -55℃ ~ +45℃; Relative humidity: daily average is not mo...
36KV Indoor High Voltage SF6 Gas Load Break Switch (LBS)
36KV Indoor High Voltage SF6 Gas Load Break Switch (LBS)
Product description BRFLN36 series indoor high-voltage SF6 load break switch, It is widely used in 36kV electric power distributio...
BRCKG5 High Voltage Vacuum Contactor 13.8KV
BRCKG5 High Voltage Vacuum Contactor 13.8KV
Overview BRCKG5-13.8 AC vacuum contactors (hereinafter referred to as: contactor) are applied in power network with AC frequency o...
Product Catalog