Product description
-
RSM6 series SF6 ring main unit, load break switch cabinet is a new generation of switching equipment based on SF6 load switch. It is widely used in 7.2~40.5kV electric power distribution system ,The products are widely used in the power supply loop or double radiation power supply system for its excellent performance and compact design and extension design concept for the purpose of making and breaking load current and overload current, can also be used for making and breaking no-load long line, no-load transformer and the capacitor etc.. The switch device adopts high performance load break switch and current limiting fuse combination ,which can replace the circuit breaker , that is, load break switch bears making and breaking kinds of load current, and limiting fuse bears greater breaking of overload current and short-circuit current .
BRSM6 series SF6 ring main unit is SF6 switch as the main switch and the entire unit adopts air insulated, suitable for power distribution automation, both compact and expandable metal enclosed switchgear, which has the characteristics of simple structure, flexible operation, convenient installation, reliable interlock etc, providing satisfactory solutions both a variety of application occasions and different user requirements. The adopting of sensor technology and the latest protection relays, coupled with advanced technical performance and easy and
flexible assembly solutions,which can fully meet the changing needs of the market. The main switch SM6 unit type SF6 ring main unit separately adopts FLN36D type or ABB produced SFG type SF6 load break switch; it can also be assembled according to the needs of users with the highest technical level of contemporary international U BP series vacuum circuit breaker or ABB produced HD4 type SF6 circuit breaker or equipped with the our company production of ZN85C-36 type vacuum circuit breaker . There are two kinds of operation modes of the main switch in the ring main unit: manual and electric. Attaching with FTU, RTU ,which can meet the requirements of "four remote". The switchgear meet the requirements of standard IEC62271-200,IEC62271-100 etc.
Service conditions
1.Altitude: Not exceed 2500m above sea level;
2.Ambient temperature:-30℃ ~ +50 , ℃
the highest temperature is not exceed 50 ; ℃
3.Ambient humidity: Daily average RH ≤ 95%;
Monthly average RH ≤ 90%
4.Earthquake intensity: ≤ 8°;
5.No flammable, explosive, no serious pollution,
No chemical corrosion and severe vibration.
Main technical parameter
|
No. |
Item |
Unit |
Parameter |
||||
|
1 |
Maximum system voltage |
kV |
12 |
15 |
24 |
40.5 |
|
|
1 |
Rated voltage |
kV |
7.2 、11 |
13.8 、15 |
17.5 、20、 22 |
30 、33、 36 |
|
|
2 |
Rated current |
A |
630/1250 |
||||
|
3 |
Rated frequency |
Hz |
50/60 |
||||
|
4 |
1min Power frequency withstand voltage |
Phase to phase, phase |
kV |
42 |
48 |
55 |
85 |
|
Fracture |
kV |
48 |
55 |
65 |
95 |
||
|
5 |
Lightning impulse withstand voltage |
Phase to phase, phase to earth |
kV |
75 |
90 |
125/150 |
170 |
|
Fracture |
kV |
85 |
105 |
150/160 |
185 |
||
|
6 |
Short time withstand current |
Main circuit |
kA |
25/2s |
|
|
Earthing circuit |
kA |
25/2s |
|||
|
7 |
Rated withstand current (peak) |
kA |
63 |
50 |
|
|
8 |
Rated transferring current |
A |
1300-1700 |
||
|
9 |
Rated load circuit making current |
A |
630 |
||
|
10 |
Rated cable(line) charging breaking current |
A |
50/10 |
||
|
11 |
No load transformer breaking current |
A |
20 |
||
|
12 |
Cable charge breaking current in earthing fault |
A |
100 |
80 |
|
|
13 |
Rated short circuit breaking current (peak) |
kA |
20 |
||
|
14 |
Rated short circuit making current (peak) |
kA |
63 |
50 |
|
|
15 |
Protection level |
|
IP4X |
||
|
16 |
Load break switch life |
times |
5000 |
||
|
17 |
Earthing switch life |
times |
5000 |
||
Outline dimension
|
|
Description |
12 kV |
24 kV |
36 kV |
|
Height(mm) |
Cabinet |
1600/1800 |
1800/2000 |
2200/2400 |
|
Width(mm) |
Cabinet |
375/500/750 |
500/650/1000 |
800/1000/1200 |
|
Deepth(mm) |
Cabinet |
840 |
1000/1150 |
1500 |
|
Weight(kg) |
|
120~260 |
180~350 |
400~800 |
Wire-Connection requirement & size
The 3 cores cable connection by making cable terminal lug.
The cable connection on the bottom through cable duct or base.
Foundation and cable trench size requirements :
The foundation shall be made of l50 × 50 × 50 angle steel or 18 channel
steel ;
The width is 900 mm, and the length is determined by the combination
size of the cabinet body;
The width of the cable trench shall ≥ 600mm, and the depth shall
≥800mm
Incomer and Outgoing : (F)
Fuse combination electrical cabinet :(F·R)
Metering cabinet :(F)